Inclined "vertical" windows in LENI, LENICALC and XML files

 To handle windows which are neither vertical nor horizontal a variation has been added to the standard. Basically the inclined window is converted into a horizontal roof-light or a vertical window:

  1. For roof slope angles larger or equal to 75° the EN 15193-1 model for vertical facade windows shall be used.
  2. For slope angles smaller than 75° the EN 15193-1 model for roof lights shall be used after a geometric adaptation of the room height and the window size in the equivalent room.

 Here is an example of before and after for type 1, where the (slightly) sloped window is converted into a vertical window:

 Here is an example of before and after where the (very) sloped window is converted into a roof- light:


Since these two variations are always connected to a wall in the building they have been implemented in LENICALC as variations on the vertical window. Here they both are in the interface and XML of the project:



In the XML a new branch SlopeParamsV (shown above) is added into the Window branch in the case where the VertWinType is 1 or 2. (0 is the normal vertical window.)

 In LeniCalc the AD areas of the different types is shown in the interface:




Friday, January 31, 2020

AD and non AD areas in a LENI calculation

Since I've fallen into this trap myself I thought I'd warn you others out there about the difference between AD and AND zones in a LENI calculation.

In a zone an AD area is an Area illuminated by Daylight. In other words the horizontal rectangle attached to the vertical window which models the area illuminated by light coming through the window from outside.

So here is a simple room with two windows and their AD rectangles in pink:

LENI AD and AND areas


The size of the rectangles (based on the size of the window generating the area) is explained in the EN 15193-1 standard itself.

The AND (Area No Daylight) is everything in the room which is not in a window's AD area, so the dark green shown below:




Lighting Energy Numeric Indicator
The trap that I sometimes fall into is I put lighting products which respond to daylight in areas which do not receive daylight! 

Here's the same room in plan view, with lighting products in AD and AND areas:

The image above illustrates how the LENI standard evaluates the energy consumption of luminaires based not only on their intrinsic consumption, but also whether they are placed in an area affected by daylight or not.

Note that putting any luminaire in a window zone will, according to the standard, reduce its consumption somewhat.











Monday, January 27, 2020

LENICALC Windows program for the EN 15193-1 standard

 LeniCalc a program for calculating the LENI standard


LENICALC is a program which does all the EN-15193-1 calculations for you, as long as you have all the right data of course. Click on the LENICALC icon on the download page:


It is free and runs on any 64 bit Windows operating system from Windows 7 and upwards.

I strongly advise that you read and do the two tutorials in this online help file before you start creating your own LeniCalc project.

Note when you install the program you'll get the Windows help file with the same tutorials, but it may be that the online version gets updated more often.